Guarding of Tanks, Fuel Storage

Regulatory Citation

NFPA 30A – Automotive and Marine Service Station Code
Origin Date 6-14-1984

What is it?

Code contains information on use of aboveground fuel storage tanks.

Who does it Apply to?

Employers involved with the production, distribution or use of flammable and combustible liquids.

How Can We Help?
Click here to learn how Asmark can help you

Overview

Fuel tanks must be capable of resisting damage from the impact of a motor vehicle or suitable collision barriers must be provided. When guard posts are installed, the following design is acceptable:

  1. Constructed of steel not less than 4 inches in diameter and filled with concrete;
  2. Not spaced more than 4 feet on center;
  3. Not less than 3 feet deep in a concrete footing of not less than 15 feet diameter; and
  4. The top of the posts should be set not less than 3 feet aboveground and should be located not less than 5 feet from the tank.